York 025-52739-000 Temperature Sensor (Water/Refrigerant) – NTC (Negative Temperature Coefficient) Thermistor Probe

York 025-52739-000 Temperature Sensor (Water/Refrigerant) – NTC (Negative Temperature Coefficient) Thermistor Probe

The 025-52739-000 is a genuine York NTC (Negative Temperature Coefficient) thermistor temperature probe designed for YLAA and YCWL air-cooled/water-cooled screw chillers. It is used to monitor chilled water inlet/outlet temperatures, cooling water temperature, discharge gas temperature, and ambient temperature.
The probe outputs a standard resistance signal to the unit's main control board for temperature monitoring, freeze protection, superheat calculation, and load regulation. Issues such as open circuits or resistance drift can lead to abnormal water temperature readings, evaporator freezing, nuisance freeze-protection shutdowns, and insufficient cooling capacity; it is an essential sensing component for screw chiller units.

Send Inquiry
Description
Argument
Products Description

Product Name York 025-52739-000 Temperature Sensor
Model 025-52739-000
Applicable Industries Construction and Commercial
Application Refrigeration compressor
Packaging Cardboard Box
MOQ 1 Piece

Product fault symptoms:
1. Panel temperature reading remains static or displays an out-of-range value (extremely high/low), with frequent temperature sensor fault alarms;
2. Inaccurate water temperature readings prevent the unit from properly adjusting its load, resulting in significant deviations in outlet temperature control;
3. Spurious triggering of freeze protection causes the unit to shut down unexpectedly, creating a risk of heat exchanger freezing;
4. Failure of discharge temperature monitoring allows the compressor to operate at high temperatures for extended periods without protection, accelerating winding degradation;
5. Damaged wire harness insulation leads to short circuits, causing the fuse in the control cabinet’s sensor circuit to blow.



Tags:

Technical parameter
Company Profile

Company Profile

Factory Profile

Factory Profile

Q1:For refrigeration industry, which brands are your products covering? A1:We produce filter element replacements for brands like,Bitzer, Carrier, York, McQuay, Trane, etc…
Q2:Does the price include freight? A2:The quotation is usually the factory price. We can recommend the most economical logistics plan and calculate the freight according to your destination and quantity.
Q3:How to ensure product quality? A3:We have a strict quality control process, and we will carry out multiple inspections before the products leave the factory to
ensure that they meet the standards.
Q4:Why choose us? A4:Product reliability: We are a professional manufacturer . can offer high-quality products at the most competitive prices.
Technical support: We provide technical assistance.
Industry experience: We have over 10 years of experience in the refrigeration equipment service field.
After-sales service: We offer professional after-sales service.
Team collaboration: We have a professional team that can provide you with prompt services and delivery schedules.

Core Product Functions:
1. Real-time monitoring of chilled/cooling water temperatures
It acquires inlet and outlet water temperatures; the main controller automatically adjusts the compressor slide valve and electronic expansion valve opening based on the temperature differential to stabilize the supply water temperature.
2. Anti-freeze protection logic
When the water temperature drops below the anti-freeze setpoint, the unit activates anti-freeze heating, fan delay, and shutdown protection to prevent the heat exchanger from freezing and cracking.
3. Compressor discharge high-temperature protection
Installed on the discharge piping to monitor discharge temperature; it implements load limiting and shutdown protection upon exceeding temperature limits to prevent compressor overheating and winding burnout.
4. Auxiliary superheat calculation for the electronic expansion valve
Utilizing high and low-pressure signals, it calculates the evaporator refrigerant superheat to precisely control the opening of the electronic expansion valve.
5. Fault self-diagnosis and feedback
In the event of probe disconnection, short circuits, or resistance drift, the control panel reports a temperature sensor fault code, enabling rapid identification of the fault location.

 