The SEN01960 is an active 24VDC high-temperature transmitter for compressor discharge lines, manufactured by Trane. Unlike standard passive NTC probes, it features a built-in signal conversion circuit board that outputs a standard industrial temperature signal; it is specifically designed for high-temperature monitoring of compressor discharge lines in large screw and air-cooled units.
The unit consists of a stainless steel immersion temperature probe and an integrated, transparent, flame-retardant control housing, equipped with a dedicated multi-pin waterproof connector. It monitors compressor discharge temperatures in real-time and transmits data to the Symbio/MCM main controller, enabling functions such as unloading or shutdown due to excessive discharge temperatures, thereby preventing refrigeration oil carbonization and compressor motor winding burnout. The circuit board, temperature-sensing core, and cable form an integrated assembly; in the event of circuit board failure, probe damage, or cable aging, the entire unit must be replaced, as individual internal components cannot be repaired separately.

Send Inquiry
Description
Argument
Products Description

Product Name Trane SEN01960 Discharge Temperature Sensor
Model SEN01960
Applicable Industries Construction and Commercial
Application Refrigeration compressor
Packaging Cardboard Box
MOQ 1 Piece

Standard Installation and Replacement Specifications:
Installation Location: Outer wall of the compressor discharge pipe; the stainless steel probe rod must be in full contact with the pipe wall and wrapped in high-temperature insulation; the control box must be kept away from high-temperature sources and heat-generating components like VFDs.

Pre-replacement Safety Procedures:
Shut down the entire unit, disconnect the 380V main power supply, and wait for the main control capacitors to fully discharge; refrigerant recovery is not required—replacement can proceed after power disconnection.

Assembly Steps:
① Unplug the waterproof multi-pin connector, remove the cable ties securing the line, and take out the old SEN01960 probe;
② Verify the model of the new probe; ensure the stainless steel probe rod is flush against the copper discharge pipe, secure it tightly with cable ties, and fully wrap the exterior with insulation material;
③ Ensure the connector latch is fully engaged and the cable is secured away from heat-generating areas (such as VFDs or contactors);
④ Power on the unit, access the maintenance menu to read the discharge temperature, and verify the reading against an infrared thermometer (a difference of ≤1.8°C is acceptable); run the unit at full load for 30 minutes to ensure stable temperature readings and the absence of false high-temperature alarms or frequent unloading faults.

Criteria for Replacement:
1. Touchscreen reports a discharge high-temperature sensor fault (no temperature reading or a fixed limit value);
2. Significant temperature drift (difference >3°C from actual measurement), causing frequent load reduction due to high temperature or false shutdowns;
3. Deformation of the stainless steel probe rod, melting of the cable jacket, or circuit board corrosion caused by water ingress or oil mist;
4. Replacement of the high-temperature probe during major unit overhauls or compressor maintenance.



Tags:

Technical parameter
Company Profile

Company Profile

Factory Profile

Factory Profile

Q1:For refrigeration industry, which brands are your products covering? A1:We produce filter element replacements for brands like,Bitzer, Carrier, Yk, McQuay, Trane, etc…
Q2:Does the price include freight? A2:The quotation is usually the factory price. We can recommend the most economical logistics plan and calculate the freight according to your destination and quantity.
Q3:How to ensure product quality? A3:We have a strict quality control process, and we will carry out multiple inspections before the products leave the factory to
ensure that they meet the standards.
Q4:Why choose us? A4:Product reliability: We are a professional manufacturer . can offer high-quality products at the most competitive prices.
Technical support: We provide technical assistance.
Industry experience: We have over 10 years of experience in the refrigeration equipment service field.
After-sales service: We offer professional after-sales service.
Team collaboration: We have a professional team that can provide you with prompt services and delivery schedules.

Internal structural materials and components:

304 stainless steel temperature-sensing probe: Conducts high exhaust temperatures while isolating against corrosion from refrigerants and oil mist;

High-precision temperature-sensing core: Captures raw temperature signals;

PCB signal conversion circuit board (core component): Handles voltage regulation, temperature compensation, and standardized signal output;

High-temperature resistant transparent epoxy resin potting layer: Secures the circuit board and provides protection against water, moisture, and oil mist;

Multi-pin waterproof locking connector: Integrated connection for 24V power supply and signal transmission, allowing for easy installation and removal.