Key Points for Product Installation and Maintenance
1. Shut down the unit, drain accumulated water from the temperature sensing well, and release pressure before removing the old probe.
2. Clean scale and sludge from inside the well to ensure the stainless steel probe rod is fully immersed in the water flow.
3. Apply a small amount of waterproof grease to the threaded connection and wrap a thin layer of PTFE tape around the exterior, taking care not to obstruct the probe rod.
4. Route shielded cables separately from high-voltage or heat-generating components—such as compressors, variable frequency drives (VFDs), and high-voltage contactors—and bundle them independently.
5. Tighten the blue nut to secure the probe rod and prevent displacement caused by unit vibration.
6. Observe correct polarity for the three-core signal cable; after installation, power on the unit (without load) while water is flowing to verify normal inlet/outlet temperature readings on the mainboard before full operation.
7. The service life is 5–8 years under standard 24-hour continuous operation; however, inspection and replacement after 5 years are recommended for units operating in environments with high scaling potential or low-temperature freeze-protection requirements.
8. When replacing the probe, simultaneously inspect and service the associated water circuit components, including the flow switch, water strainer, and KIT07614 filter drier.
Tags: Chiller temperature probe commercial air conditioning sensor compressor temperature component cooling system control sensor HVAC maintenance spare parts HVAC thermistor industrial chiller replacement parts refrigeration system accessories refrigeration temperature detector SEN00306 Trane Spare Parts Trane temperature sensor
Technical parameter

Company Profile

Factory Profile
| Q1:For refrigeration industry, which brands are your products covering? | A1:We produce filter element replacements for brands like,Bitzer, Carrier, Yk, McQuay, Trane, etc… |
| Q2:Does the price include freight? | A2:The quotation is usually the factory price. We can recommend the most economical logistics plan and calculate the freight according to your destination and quantity. |
| Q3:How to ensure product quality? | A3:We have a strict quality control process, and we will carry out multiple inspections before the products leave the factory to ensure that they meet the standards. |
| Q4:Why choose us? | A4:Product reliability: We are a professional manufacturer . can offer high-quality products at the most competitive prices. Technical support: We provide technical assistance. Industry experience: We have over 10 years of experience in the refrigeration equipment service field. After-sales service: We offer professional after-sales service. Team collaboration: We have a professional team that can provide you with prompt services and delivery schedules. |
Scenarios Requiring Sensor Replacement
1. Mainboard water temperature reading remains static or fluctuates erratically; significant discrepancy between actual water circuit temperature and the displayed value;
2. Unit frequently reports water temperature sensor faults; compressor load is limited, preventing full-capacity cooling;
3. Winter freeze-protection logic fails; water pump fails to activate for heating despite low return water temperature;
4. Stainless steel probe rod suffers from scaling or corrosion-induced perforation; temperature sensing sensitivity is severely compromised;
5. Cable insulation is damaged, shielding is broken, or connectors leak water, causing signal interference and instability;
6. Thermistor is burnt out (infinite resistance or short circuit), resulting in a complete loss of temperature feedback.