Products Description

| Product Name | Yk 025-41756-002 Pressure Sensor |
| Model | 025-41756-002 |
| Applicable Industries | Construction and Commercial |
| Application | Refrigeration compressor |
| Packaging | Cardboard Box |
| MOQ | 1 Piece |
York 025-41756-002 Pressure Sensor: Core Functions
1. Precise Monitoring of Suction / Low-Pressure Side
Specifically designed to measure pressure at the evaporator outlet and compressor suction port; calculates corresponding saturation temperatures to prevent low-pressure trips, evaporator freezing, and suction superheating.
When paired with a high-pressure sensor, it calculates pressure ratios, pressure differentials, and superheat levels, providing essential data for the precise regulation of guide vanes or slide valves.
2. System Protection (Core Safety Feature)
Low-Pressure Protection: Triggers an alarm or system shutdown if pressure drops below a preset threshold (e.g., 20 PSIG), preventing evaporator freezing and compressor oil starvation.
Suction Superheat Protection: Detects abnormal pressure readings—and consequently abnormal saturation temperatures—to provide early warnings regarding liquid carryover in the return gas and the risk of liquid slugging.
Flow / Load Monitoring: Pressure fluctuations serve as indicators of anomalies in water or refrigerant flow, clogged filters, or valve malfunctions.
3. Control and Energy Efficiency
Capacity Modulation: For centrifugal chillers, guide vanes—and for screw chillers, slide valves—automatically adjust to match the system load based on suction pressure, thereby stabilizing the chilled water outlet temperature and reducing energy consumption.
Fault Diagnosis: Detects signal drift, signal stagnation, or sudden signal jumps to provide early warnings regarding sensor aging, connector leaks, damaged wiring harnesses, or main controller malfunctions.
4. High Reliability
All-Stainless Steel Housing: Highly resistant to vibration and corrosion; compatible with refrigerants such as R134a, R513A, and R407C.
Laser Welding + Hermetic Sealing: Ensures long-term leak-free operation and provides excellent resistance to temperature extremes and aging.
Factory Calibrated: Operates on a 5VDC power supply with a linear output range of 0.5–4.5V; features “plug-and-play” functionality requiring no field calibration.
Tags: air conditioning pressure sensor chiller maintenance parts chiller pressure sensor chiller replacement sensor commercial HVAC sensor cooling system pressure sensor hvac pressure sensor HVAC spare component HVAC Spare Parts industrial chiller sensor industrial pressure sensor pressure sensor pressure transducer refrigerant pressure sensor refrigeration equipment sensor refrigeration pressure sensor York 025-41756-002 York chiller parts York HVAC accessories York sensor
Technical parameter

Company Profile

Factory Profile
| Q1:For refrigeration industry, which brands are your products covering? | A1:We produce filter element replacements for brands like,Bitzer, Carrier, York, McQuay, Trane, etc… |
| Q2:Does the price include freight? | A2:The quotation is usually the factory price. We can recommend the most economical logistics plan and calculate the freight according to your destination and quantity. |
| Q3:How to ensure product quality? | A3:We have a strict quality control process, and we will carry out multiple inspections before the products leave the factory to ensure that they meet the standards. |
| Q4:Why choose us? | A4:Product reliability: We are a professional manufacturer . can offer high-quality products at the most competitive prices. Technical support: We provide technical assistance. Industry experience: We have over 10 years of experience in the refrigeration equipment service field. After-sales service: We offer professional after-sales service. Team collaboration: We have a professional team that can provide you with prompt services and delivery schedules. |
Common Product Faults and Replacement Criteria
1. Signal fixed at 0.5V: Short circuit on the low-voltage side / Damaged sensor;
2. Signal fixed at 4.5V: Open circuit on the high-voltage side / Damaged sensor;
3. Drifting readings / Significant fluctuations: Leaking connector, aged seals, loosening due to vibration;
4. Exceeded service life (≥5 years): Zero-point drift, reduced accuracy; preventive replacement recommended.