Carrier 02XR05001501 electric heating element for 19XR centrifugal chiller crankcase oil heater; stainless steel construction.

Carrier 02XR05001501 electric heating element for 19XR centrifugal chiller crankcase oil heater; stainless steel construction.

The 02XR05001501 is a dedicated immersion-type crankcase oil heater for Carrier 19XR series centrifugal chillers. Part of the 02XR compressor accessory line, it is rated for 115VAC, 60Hz operation.
It features a seamless stainless steel heating sheath, an internal nickel-chromium heating element, and high-temperature magnesium oxide insulation. Designed with a threaded seal at the terminal end, it is fully submerged in the compressor oil sump. During unit shutdown or standby, it continuously heats the lubricating oil to minimize refrigerant absorption and improve oil fluidity at low temperatures; this fundamentally prevents liquid slugging and compressor seizure caused by dry running or lubrication failure, making it a critical safety component of the centrifugal chiller's lubrication system.
Constructed as an integrated sealed assembly, the entire unit must be replaced in the event of a broken heating element, sheath corrosion or perforation, a blown internal thermal fuse, or damage to the power leads.

Send Inquiry
Description
Argument
Products Description

oplus_262176

Product Name Carrier 02XR05001501 electric heating element
Model 02XR05001501
Applicable Industries Construction and Commercial
Application Refrigeration compressor
Packaging Cardboard Box
MOQ 1 Piece

Core Product Advantages:
Pre-heating lubricating oil during shutdown to separate and release dissolved refrigerant (Core Function)
Continuous heating during unit standby significantly reduces refrigerant solubility in POE oil, allowing liquid refrigerant to separate and return to the evaporator; this prevents large amounts of refrigerant from entering the compressor with the oil upon startup, thereby eliminating rotor and bearing damage caused by liquid slugging or erosion.

Reducing oil viscosity in low-temperature environments to ensure proper oil pressure at startup
After low-temperature shutdowns in winter, pre-heating lowers the oil’s viscosity, enabling the oil pump to rapidly reach standard operating pressure upon startup; this prevents compressor damage (such as scoring) caused by dry running without adequate lubrication.

304 seamless stainless steel casing: resistant to leakage and corrosion during long-term immersion
The seamless, integrated design eliminates the risk of weld-seam leakage; the casing withstands long-term immersion in acidic oil mixtures (resulting from refrigerant decomposition) without wall perforation or oil leakage.

Built-in dry-burn thermal fuse protection to eliminate fire hazards in the equipment room
In the event of low oil levels or dry-burning (where the heating element is exposed), a built-in fuse permanently cuts off the heating circuit; this prevents high temperatures from igniting the refrigeration oil, ensuring compliance with commercial equipment room fire safety regulations.



Tags:

Technical parameter
Company Profile

Company Profile

Factory Profile

Factory Profile

Q1:For refrigeration industry, which brands are your products covering? A1:We produce filter element replacements for brands like,Bitzer, Carrier, Yk, McQuay, Trane, etc…
Q2:Does the price include freight? A2:The quotation is usually the factory price. We can recommend the most economical logistics plan and calculate the freight according to your destination and quantity.
Q3:How to ensure product quality? A3:We have a strict quality control process, and we will carry out multiple inspections before the products leave the factory to
ensure that they meet the standards.
Q4:Why choose us? A4:Product reliability: We are a professional manufacturer . can offer high-quality products at the most competitive prices.
Technical support: We provide technical assistance.
Industry experience: We have over 10 years of experience in the refrigeration equipment service field.
After-sales service: We offer professional after-sales service.
Team collaboration: We have a professional team that can provide you with prompt services and delivery schedules.

Internal structural materials of the product:
304 seamless stainless steel heating sheath (primary component for heat conduction and pressure containment);

High-temperature resistant nickel-chromium alloy heating resistance wire;

High-purity magnesium oxide insulation and thermal conduction filler layer;

Built-in one-time thermal fuse for overheat protection;

Oil- and high-temperature-resistant dual-core power cable; threaded sealing mounting section.