The HH79NZ047 is a high-precision, direct-insertion temperature sensing element specifically designed for Carrier industrial chillers and centrifugal/screw compressors. Its primary function is to provide real-time monitoring of critical operating parameters, such as compressor discharge temperature, lubricant oil temperature, refrigerant liquid line/suction temperature, and condenser/evaporator temperature. It converts temperature signals into linear resistance or voltage signals, which are then fed back to the unit controller to facilitate five core functions: temperature protection, load regulation, oil temperature control, anti-freeze protection, and energy efficiency optimization. As such, it serves as a pivotal temperature control component for ensuring the safe and efficient operation of the unit.

Send Inquiry
Description
Argument
Products Description

Product Name Carrier Temperature Sensor HH79NZ047
Model HH79NZ047
Applicable Industries Construction and Commercial
Application Refrigeration compressor
Packaging Cardboard Box
MOQ 1 Piece

Carrier HH79NZ047 Temperature Sensor: Compatible Unit Series
1. Centrifugal Chillers: 19XL, 19XR, 19XRD, 19XRS Series
2. Screw Chillers: 30HX, 30HXC, 30HXY, 30XW, 30XA, 30XQ Series
3. Reciprocating Compressors: 06E, 06D, 06NW, 06NA Series
4. Industrial Refrigeration Units: 16JB, 18JB Series Industrial Freezers



Tags:

Technical parameter
Company Profile

Company Profile

Other Product Images

Other Product Images

Factory Photos

Factory Photos

Q1:For refrigeration industry, which brands are your products covering? A1:We produce filter element replacements for brands like,Bitzer, Carrier, York, McQuay, Trane, etc…
Q2:Does the price include freight? A2:The quotation is usually the factory price. We can recommend the most economical logistics plan and calculate the freight according to your destination and quantity.
Q3:How to ensure product quality? A3:We have a strict quality control process, and we will carry out multiple inspections before the products leave the factory to
ensure that they meet the standards.
Q4:Why choose us? A4:Product reliability: We are a professional manufacturer . can offer high-quality products at the most competitive prices.
Technical support: We provide technical assistance.
Industry experience: We have over 10 years of experience in the refrigeration equipment service field.
After-sales service: We offer professional after-sales service.
Team collaboration: We have a professional team that can provide you with prompt services and delivery schedules.

Product Functions and Benefits
1. Compressor Discharge Temperature Monitoring: Prevents excessive discharge temperatures, thereby preventing burnout of the motor and bearings.
Lubricant Temperature Control: Maintains oil temperature within the optimal range of 35–65°C to ensure proper lubrication, minimize wear, and extend the compressor’s service life.
2. Refrigerant Suction / Liquid Line Temperature Monitoring: Facilitates the control of the electronic expansion valve, regulates cooling capacity, and prevents wet compression and liquid slugging.
3. Evaporator / Condenser Temperature Monitoring: Enables anti-freeze protection, optimizes condensing temperatures, and enhances energy efficiency.
4. Fault Diagnosis and Early Warning: Generates specific fault codes in the event of temperature anomalies, facilitating rapid troubleshooting and maintenance.
5. Unit Load Regulation: Links temperature signals to slide valve or variable frequency controls to deliver cooling capacity on demand, resulting in energy savings of over 15%.
Fault Diagnosis:
1. Fixed Resistance Value: Indicates a short circuit or open circuit within the sensor.
2. Temperature Unresponsive to Operating Conditions: Indicates a failure of the NTC sensing element.
3. Reading Fluctuations > ±1°C: Indicates a loose connector, moisture ingress, or electromagnetic interference.