Products Description

| Product Name | Carrier 00PPG000030600 Electronic Pressure Sensor |
| Model | 00PPG000030600 |
| Applicable Industries | Construction and Commercial |
| Application | Refrigeration compressor |
| Packaging | Cardboard Box |
| MOQ | 1 Piece |
Core Product Functions:
1. Real-time High-Pressure Discharge Monitoring and Display
Continuously monitors discharge high pressure at the condenser and compressor, transmitting linear voltage signals to the CCM main controller. The control panel displays real-time pressure values, facilitating O&M assessment of refrigerant charge levels and heat exchange conditions.
2. Energy-Saving Staged Control of Condenser Fans
The mainboard automatically starts/stops fans and adjusts the number of active condenser fans based on high-pressure readings. It reduces fan power consumption during low loads and increases airflow during high-temperature, full-load operation, thereby stabilizing high-side pressure and reducing the likelihood of high-pressure protection shutdowns.
3. Staged High-Pressure Warning and Protection
When high pressure approaches warning thresholds, the unit preemptively limits slide valve loading and reduces compressor output. Excessive pressure triggers an interlock shutdown; combined with a mechanical high-pressure switch, this establishes a dual-layer safety protection system.
4. Closed-Loop Load Regulation via Screw Compressor Slide Valve
Linked to the chilled water outlet temperature, the system automatically adjusts the slide valve opening (0–100%) to balance the cooling load against system high-side pressure, minimizing unit surging and drastic fluctuations in high and low pressures.
5. Precise Fault Self-Diagnosis and Reporting
The main controller detects anomalies—such as open circuits, short circuits, or signals outside standard ranges—and reports high-pressure sensor faults. The unit locks out loading operations, enabling rapid identification of wiring or sensor failures.
Tags: 00PPG000030600 Carrier chiller spare parts Carrier high pressure sensor central chiller maintenance spare part chiller high pressure transducer commercial air conditioning pressure fitting compressor protection accessory cooling system overpressure monitoring component HVAC pressure probe industrial refrigeration replacement sensor refrigerant pipeline pressure sensor refrigeration high pressure detector
Technical parameter

Company Profile

Factory Profile
| Q1:For refrigeration industry, which brands are your products covering? | A1:We produce filter element replacements for brands like,Bitzer, Carrier, York, McQuay, Trane, etc… |
| Q2:Does the price include freight? | A2:The quotation is usually the factory price. We can recommend the most economical logistics plan and calculate the freight according to your destination and quantity. |
| Q3:How to ensure product quality? | A3:We have a strict quality control process, and we will carry out multiple inspections before the products leave the factory to ensure that they meet the standards. |
| Q4:Why choose us? | A4:Product reliability: We are a professional manufacturer . can offer high-quality products at the most competitive prices. Technical support: We provide technical assistance. Industry experience: We have over 10 years of experience in the refrigeration equipment service field. After-sales service: We offer professional after-sales service. Team collaboration: We have a professional team that can provide you with prompt services and delivery schedules. |
Product fault symptoms:
The unit reports a high-pressure sensor fault immediately upon power-up and self-test; the high-pressure reading on the panel drops to zero, freezes, or drifts significantly;
Condenser fan start/stop logic is erratic; high pressure spikes continuously during full-load summer operation, causing frequent high-pressure shutdowns;
Slide valve loading is sluggish, resulting in insufficient cooling capacity and chilled water outlet temperatures failing to meet specifications;
Water ingress and corrosion at the Packard connector cause intermittent loss of pressure signals and random unit load limiting;
Diaphragm rupture leads to refrigerant leakage at the threaded base; both high and low system pressures are consistently low, indicating a persistent refrigerant shortage;
Internal circuitry has aged, causing false alarms and shutdowns before the high-pressure protection threshold is actually reached.